M0 file - rio device inhibit control -17, M0 file - rio device inhibit control, Important – Rockwell Automation 1747-SN Remote I/O Scanner User Manual
Page 61: M0 (control) file - rio device control words
![background image](/manuals/579975/61/background.png)
Publication 1747-UM013B-EN-P - January 2005
Scanner Configuration and Programming 4-17
M0 File - RIO Device Inhibit Control
M0 Words 8 through 11 - you use these words to command the
scanner to stop scanning logical racks 0, 1, 2, and 3. Bits 0 to 3 in each
word correspond to I/O group locations within logical racks 0, 1, 2,
and 3.
To stop scanning (inhibit) a device listed in the configuration (G) file,
set the bit corresponding to the starting group address of the device to
1. Setting bits that do not correspond to the device logical starting
group address will not inhibit the device. To resume scanning a
device, reset the bit (which corresponds to the starting group address
of the device) to 0.
Inhibiting a device does not affect the current settings of the Device
Fault Status (words 12 to 15 of the M1 file). Inhibited devices
eventually time out and either return to their last state or reset
(depending on the device’s last state setting).
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Bit Number
0
1
1
0
x
x
x
x
x
x
x
x
x
x
x
x
Logical Rack 0 Device Inhibit Word 8
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
1
0
0
1
x
x
x
x
x
x
x
x
x
x
x
x
1
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
Logical Rack 1 Device Inhibit Word 9
Logical Rack 2 Device Inhibit Word 10
Logical Rack 3 Device Inhibit Word 11
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
Logical Rack 0 Device Reset Word 16
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
Logical Rack 1 Device Reset Word 17
Logical Rack 2 Device Reset Word 18
Logical Rack 3 Device Reset Word 19
1
0
0
1
x
x
x
x
x
x
x
x
x
x
x
x
Logical Rack 0 Remote Output Reset Word 24
1
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
1
0
0
x
x
x
x
x
x
x
x
x
x
x
x
0
1
0
0
x
x
x
x
x
x
x
x
x
x
x
x
Logical Rack 1 Remote Output Reset Word 25
Logical Rack 2 Remote Output Reset Word 26
Logical Rack 3 Remote Output Reset Word 27
M0 (Control) File - RIO Device Control Words
e = slot number of the SLC rack containing the scanner
x = bit not used/defined
Device
Inhibit
Control
Device
Reset
Control
Output
Reset
Control
M0:e.8
M0:e.9
M0:e.10
M0:e.11
M0:e.12
M0:e.13
M0:e.14
M0:e.15
M0:e.16
M0:e.17
M0:e.18
M0:e.19
IMPORTANT
Control functions (i.e., device inhibit, device reset,
and device output reset) are only selectable for the
primary device, but also apply to the complementary
device. Control functions for complementary devices
cannot be exclusively enabled.