beautypg.com

Rockwell Automation 1747-SN Remote I/O Scanner User Manual

Page 23

background image

Publication 1747-UM013B-EN-P - January 2005

Overview 1-15

Summary for Placing Modules Used In Complementary I/O

Discrete Modules

Block Transfer Modules

The following example illustrates how I/O modules requiring two
words of the input or output image can leave unused image space.

Addressing Method

Types of Modules used

Placement

2-slot

8-point

Install input modules
opposite output modules,
and output modules
opposite input modules.

(1)

(1) If an input module resides in either slot associated with a logical group of the primary chassis, an input module

cannot reside in that logical group’s complementary chassis.

1-slot

8-point, 16-point

1/2-slot

8-point, 16-point, 32-point

Addressing Method

Placement

2-slot

The right slot of the primary I/O group can be another block
transfer module, or an 8-point input or output module.

The left slot of the complementary I/O group must be empty.

In the right slot of the complementary I/O group, you can place
an 8-point output module; this slot must be empty if the
corresponding slot in the primary I/O group is a block transfer
module.

1-slot

Leave the corresponding I/O group in the complementary
chassis empty.

1/2-slot

Leave the corresponding I/O group in the complementary
chassis empty.