Scanner Configuration and Programming 4-7

Rules for Configuring the Scanner

General

• The smallest portion of the scanner’s I/O image that can be

allocated to a single RIO device is two logical groups (1/4
logical rack).

• If a device is configured in word 1, there must be image

allocated to it in word 2. This rule also applies to words 3 and 4
with the following exception: if word 3 = 1 and word 4 = 0, the
complementary mode is selected even though no
complementary devices are configured.

• A logical device’s starting group must begin at even group

numbers (0, 2, 4, or 6). Each bit in words 2 and 4 represent an
even logical group number.

Concerning Complementary I/O

• It is valid for you to have a complementary device configured

even if no associated primary device exists. Also,
complementary devices do not have to be the same logical
image size as the primary device.

• G file words 1 and 2 can both be zero (no primary devices).

However, in this case there must be at least one complementary
device configured in G file words 3 and 4.