Publication 1747-UM013B-EN-P - January 2005

Overview 1-3

your application program requires. Configuration is done through the
confiGuration file (G file). Refer to Chapter 4, Configuration and
Programming, for more information.

Scanner I/O Image Division

The scanner allows each adapter to use a fixed amount (user defined)
of the scanner’s input and output image. Part of the SLC processor’s
image is used by local I/O, the other portion is used by the scanner
for remote I/O.

The scanner remote I/O image is divided into logical racks and further
divided into logical groups. A full logical rack consists of eight input
and eight output image words. A logical group consists of one input
and one output word in a logical rack. Each logical group is assigned
a number from 0 to 7.

IMPORTANT

The SLC 500 processor (SLC 5/02 or later) supports
multiple scanners in its local I/O chassis. The
maximum number is dependent on the following:

• backplane power requirements (power supply

dependent)

• SLC 500 processor I/O data table limit (4,096 I/O)
• processor memory to support the application

(SLC 500 processor dependent)

Processor I/O Image

Scanner I/O Image

Adapter

Image

Logical Group 7

Local I/O

Remote I/O

(Scanner Image)

Logical Rack 2

Logical Rack 1

Logical Rack 0

Logical Group 0