Publication 1747-UM013B-EN-P - January 2005

A-14 Specifications

number of logical devices on the RIO network affects only TRIO, and
only affects TSNo when additional logical racks are used.

When complementary mode is selected, the number of configured
racks is also determined by the number of primary or complementary
racks configured, but not by both. (The maximum number of
configured racks
is 4.) That is, if there is a primary rack configured with a
corresponding complementary rack, that is considered one logical
rack. If there is a primary rack configured without a complementary
rack (or vice versa), that also is considered one logical rack.

TSNo without M0 File Writes

Normal Mode

(1)

(1) All times shown are in milliseconds (ms).

Number of Logical
Racks Configured

All Baud Rates

T

SNo

if T

upd

≤ T

hold

T

hold

T

SNo

if T

upd

>T

hold

1 Logical Rack

5.0

5.0

2.5

2 Logical Rack

7.0

7.0

4.0

3 Logical Rack

9.0

9.0

5.5

4 Logical Rack

11.0

11.0

7.0

Complementary

(1)

(2)

Number of Logical
Racks Configured

57.6K baud

115.2K baud

230.4K baud

T

SNo

if

T

upd

≤ T

hold

T

hold

T

SNo

if

T

upd

>T

hold

T

SNo

if

T

upd

≤ T

hold

T

hold

T

SNo

if

T

upd

>T

hold

T

SNo

if

T

upd

≤ T

hold

T

hold

T

SNo

if

T

upd

>T

hold

1 Logical Rack

6.0

5.0

4.0

7.0

7.0

4.0

10.0

9.0

4.0

2 Logical Rack

9.0

8.0

5.0

10.0

10.0

6.0

12.0

12.0

7.0

3 Logical Rack

12.0

11.0

7.0

12.0

12.0

8.0

16.0

16.0

10.0

4 Logical Rack

15.0

14.0

9.0

16.0

16.0

10.0

21.0

22.0

13.0

(1) All times shown are in milliseconds (ms).

(2) Although a faster baud rate decreases RIO scan time (T

RIO

), it has an inverse affect on T

SNo

when complementary I/O mode is selected.