Publication 1747-UM013B-EN-P - January 2005

Overview 1-17

Complementary I/O Application Considerations

If you configure a complementary device to use more I/O image
space than an associated primary device, then block transfers can only
be performed to locations in the complementary device that have
associated I/O image space in the primary device. For example, if a
primary device is 1/2 logical rack and a complementary device is a full
logical rack, block transfers can be performed only in the first 1/2
logical rack of the complementary device. Attempting block transfers
in the last half of the complementary device will result in a BT error
(error - 11 - device not configured).

Complementary 1771 I/O Module Details

Use the following modules in either primary or complementary I/O
chassis opposite any type of module:

• Communication Adapter Module (1771-KA2)
• Communication Controller Module (1771-KE)
• PLC-2 Family/RS-232-C Interface Module (1771-KG)
• Fiber Optics Converter Module (1771-AF)
• DH/DH+ Communication Adapter Module (1785-KA)
• DH+/RS-232C Communications Interface Module (1785-KE)

Use the following modules in either primary or complementary I/O
chassis opposite any type of module. However, these modules do not
work as stand-alone modules; each one has an associated master
module. Use care when placing the master modules in the I/O chassis:

• Analog Input Expander Module (1771-E1, -E2, -E3)
• Analog Output Expander Module (1771-E4)
• Servo (Encoder Feedback) Expander Module (1771-ES)
• Pulse Output Expander Module (1771-OJ)

Word 7

Word 5
Word 6

Word 3

Word 1

Word 2

Word 0

Word 4

Logical
Rack 8

Word 7

Word 5
Word 6

Word 3
Word 4

Word 1

Word 2

Word 0

Logical
Rack 0

1/2 logical rack
configured and
usable

1/2 logical rack not
configured

1/2 logical rack
configured and usa

1/2 logical rack
configured, but not
usable for BT since
Words 4-7 are not
configured for the
primary device.

1/2 logical rack
configured and usable

1/2 logical rack
configured, but not
usable for BT since
Words 4 to 7 are not
configured for the
primary device.