beautypg.com

Scanner operation, Scanner operation -8, At power up -8 in run mode -8 – Rockwell Automation 1747-SN Remote I/O Scanner User Manual

Page 42: When changing from run mode -8, At power up, When changing from run mode, Scanner

background image

Publication 1747-UM013B-EN-P - January 2005

3-8 Installation and Wiring

2. Make sure you have configured your SLC processor and

downloaded an application program. (Refer to chapter 4.)

3. Make sure power is applied to all devices on the RIO link.

Scanner Operation

Below is a description of the scanner’s operation at power up, run
mode, and when changing from run mode to program or test mode.

At Power Up

At power up, the scanner’s communication LED (green LED) is off
until the SLC is changed to Run or Test mode.

In Run Mode

During normal scanner operation (SLC in Run mode), the scanner’s
LEDs illuminate as shown below:

When Changing From Run Mode

When the SLC processor is changed from Run mode, to Program or
Test mode the following occurs:

• scanner’s COMM LED remains green.
• the scanner continues to read its input devices and send output

data to its RIO adapters.

• the scanner instructs adapters to either clear all outputs or hold

them in their last state (depending on their configuration). Refer
to the user manual included with each RIO device for specific
information relating to the Hold Last State setting.

FAULT LED is off.

COMM LED is green.

SCANNER

FAULT

COMM