1769-sm1 settings, Compactlogix example program – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual
Page 75
CompactLogix Ladder Example Program
6-3
The 1769-SM1 used in the example program has the following
parameter settings:
Note that the module must be reset using Parameter 02 - [Reset
Module] before these parameter settings take effect.
for information about the I/O Image layout, Channel
Enable/Status, Logic Command/Status, Reference/Feedback, and
Datalinks.
1769-SM1 Settings
Parameter
Setting
Description
No.
Name
07
I/O Config 1
11111
CH1 Command/Status and all Datalinks are enabled
24
I/O Config 2
11111
CH2 Command/Status and all Datalinks are enabled
41
I/O Config 3
11111
CH3 Command/Status and all Datalinks are enabled
!
ATTENTION: Risk of injury or equipment damage exists.
If the module is transmitting I/O that controls the drive, the
drive may fault when you reset the module. Determine how
your drive will respond before resetting the module.
CompactLogix Example Program
Figure 6.2 CompactLogix Ladder Logic Main Program
CompactLogix w/ 1769-SM1 DPI/SCANport Module example program
Execute the 1769-SM1 Channel 1 subroutine.
0
Jump To Subroutine
Routine Name Channel_1
JSR
CompactLogix w/ 1769-SM1 DPI/SCANport Module example program
Execute the 1769-SM1 Channel 1 subroutine.
Execute the 1769-SM1 Channel 2 subroutine.
1
Jump To Subroutine
Routine Name Channel_2
JSR
Execute the 1769-SM1 Channel 2 subroutine.
Execute the 1769-SM1 Channel 3 subroutine.
2
Jump To Subroutine
Routine Name Channel_3
JSR
Execute the 1769-SM1 Channel 3 subroutine.
(End)