Parameter mode – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual
Page 43
Configuring the Module
3-13
When the Configuration Mode switch is in the “Parameter” position, the
1769-SM1 uses its internal parameters setting to configure the module.
Any configuration data downloaded by the controller will be ignored.
Important: When the Parameter mode is used, the configuration data size
in the controller should be set to “0.” Refer to
for more information.
Only DPI products (PowerFlex 70, etc.) can utilize this feature since DPI
peripheral devices (HIMs, DriveExplorer with 1203-SSS converter, etc.)
can access the 1769-SM1 directly. Allowing DPI peripherals to change
the configuration settings makes the Parameter mode more flexible and
simpler to use than Controller mode.
Figure 3.15 DriveExplorer Window with Mapped 1769-SM1 Compact I/O Module
Parameter Mode
Table 3.B Module Configuration Data Words in Parameter Mode
Description
CH1
Parameter
CH2
Parameter
CH3
Parameter
I/O Config
7
24
41
Idle Action
9
26
43
Fault Config. Logic Command
10
27
44
Fault Config. Reference
11
28
45
Fault Config Datalink In A1
12
29
46
Fault Config Datalink In A2
13
30
47
Fault Config Datalink In B1
14
31
48
Fault Config Datalink In B2
15
32
49
Fault Config Datalink In C1
16
33
50
Fault Config Datalink In C2
17
34
51
Fault Config Datalink In D1
18
35
52
Fault Config Datalink In D2
19
36
53