Chapter 2, Installing the module, Preparing for an installation – Rockwell Automation 1769-SM1 Compact I/O to DPI/SCANport Module User Manual
Page 21: 2installing the module
![background image](/manuals/579881/21/background.png)
Chapter
2
Installing the Module
Chapter 2 provides instructions for installing the 1769-SM1 module as
an expansion I/O module on MicroLogix 1500 and CompactLogix
controllers, or with a remote 1769-based adapter.
Consider the following when installing the 1769-SM1 module:
• Verify that you have all required equipment. Refer to
.
• A MicroLogix 1500 Base Unit or Compact I/O power supply has
limits in the amount of +5V dc and +24V dc current it can supply to
modules in its I/O bank. These limits depend on the catalog number
(e.g. 1769-PA2) of the supply. A bank of modules must not exceed
the current limits of the MicroLogix 1500 Base Unit or I/O bank
power supply.
Refer to the MicroLogix 1500 User Manual (Publication No.
1764-UM001…), or the Compact 1769 Expansion I/O Power
Supplies Installation Instructions (Publication No. 1769-5.14).
• The 1769-SM1 module has a distance rating of six, therefore the
module must be within six modules of the I/O bank’s power supply.
Topic
Page
Topic
Page
Selecting the Configuration Mode
Connecting the Module to the Drive 2-9
Assembling the Module to the Controller 2-3
Preparing for an Installation
!
ATTENTION: Risk of equipment damage exists. The 1769-SM1
module contains ESD (Electrostatic Discharge) sensitive parts that can
be damaged if you do not follow ESD control procedures. Static control
precautions are required when handling the module. If you are
unfamiliar with static control procedures, refer to Guarding Against
Electrostatic Damage, Publication 8000-4.5.2.