6-2
CompactLogix Ladder Example Program
Explicit messaging (parameter read/write) capability varies between
CompactLogix controllers:
The PowerFlex 70 drives used in the example program have the
following parameter settings:
Note that the Data Out settings are set to match the respective Data In
settings for demonstration purposes only. This allows read/write
capability for the eight parameters selected and provides the ability to
verify that a change was made to a parameter value.
Controller Used With 1769-SM1
Supports Explicit Messaging
Yes
No
CompactLogix 1769-L20
✔
CompactLogix 1769-L30
✔
CompactLogix 1769-L32E
✔
CompactLogix 1769-L35E
✔
PowerFlex 70 Settings
Parameter
Setting
Description
No.
Name
90
Speed Ref A Sel
19
“DPI Port 2”
300
Data In A1
140
Parameter 140 - [Accel Time 1]
301
Data In A2
142
Parameter 142 - [Decel Time 1]
302
Data In B1
100
Parameter 100 - [Jog Speed]
303
Data In B2
155
Parameter 155 - [Stop Mode A]
304
Data In C1
101
Parameter 101 - [Preset Speed 1]
305
Data In C2
102
Parameter 102 - [Preset Speed 2]
306
Data In D1
103
Parameter 103 - [Preset Speed 3]
307
Data In D2
104
Parameter 104 - [Preset Speed 4]
310
Data Out A1
140
Parameter 140 - [Accel Time 1]
311
Data Out A2
142
Parameter 142 - [Decel Time 1]
312
Data Out B1
100
Parameter 100 - [Jog Speed]
313
Data Out B2
155
Parameter 155 - [Stop Mode A]
314
Data Out C1
101
Parameter 101 - [Preset Speed 1]
315
Data Out C2
102
Parameter 102 - [Preset Speed 2]
316
Data Out D1
103
Parameter 103 - [Preset Speed 3]
317
Data Out D2
104
Parameter 104 - [Preset Speed 4]