Example 2 - indirect addressing, Example 2 - indirect addressing -7 – Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual
Page 99
Publication 1746-UM002B-EN-P - August 2004
Application Examples 6-7
Data Table for N10 File (hexidecimal)
Data Table for N11 File (decimal)
Example 2 - Indirect
Addressing
In this example, the module is set up in Class 4, mode 1 using only
two counters. This example uses indirect addressing, which is
compatible only with SLC 5/03 or higher processors.
Programming Blocks
Offset
0
1
2
3
4
5
6
7
8
9
Module Setup
N10:0
1
103
8
0
0
0
0
0
0
0
Counter Configuration
N10:10
F02
6
0
6
0
0
0
0
0
0
Min/Max Count Value Counter 1
N10:20
4
0
0
0
190
0
0
0
0
0
Min/Max Count Value Counter 2
N10:30
104
0
0
0
1F4
0
0
0
0
0
Min/Max Count Value Counter 3
N10:40
204
0
0
0
258
0
0
0
0
0
Min/Max Count Value Counter 4
N10:50
304
0
0
0
2BC
0
0
0
0
0
Program Ranges
N10:60
10
1
0
0
0
31
1
0
0
0
Program Ranges
N10:70
10
2
0
32
0
63
2
0
0
0
Program Ranges
N10:80
10
4
0
64
0
95
4
0
0
0
Program Ranges
N10:90
10
8
0
96
0
C7
8
0
0
0
Program Ranges
N10:100
10
10
0
C8
0
F9
1
0
0
0
Program Ranges
N10:110
10
20
0
FA
0
12B
2
0
0
0
Program Ranges
N10:120
10
40
0
12C
0
15D
4
0
0
0
Program Ranges
N10:130
10
80
0
15E
0
190
8
0
0
0
Counter Control
N10:140
80
8001
8001
8001
8001
FF00
FF
0
0
0
N10:150
0
0
0
0
0
0
0
0
Offset
0
1
2
3
4
5
6
7
8
9
N11:0
140
140
14
TIP
This example may be used with any mode (1, 2, or
3) and with any SLC 5/03 or higher processor, as
long as the module is in a local chassis. However,
the N10 and N11 data files would need to be
modified for a different configuration.