Rockwell Automation 1746-HSCE2 Multi-Channel High Speed Counter Module User Manual
Page 90
Publication 1746-UM002B-EN-P - August 2004
5-8 Start Up, Operation, Troubleshooting, and Debug Mode
Figure 5.3 Required Bits for Module Setup and Counter Configuration Blocks
The debug view of this block shows the range allocation of all four
counters. The fourth counter is shown in word 5. The PRA bit
(word 0, bit 08) is never set.
In the Counter Configuration Block
The required bits for debug mode in the Counter Configuration Block
are the transmit bit, the debug bit, and the block type byte. Bits 13
and 14 must be zero. The values of words 1 through 7 are ignored by
the module while in debug mode. The PGM(n) bits (word 0, bits 08 to
11) are never set in this block.
Figure 5.4 Required Bits for Counter Configuration Block
In the Minimum/Maximum Count Value Block
For this block, the transmit bit, the debug bit, the block type byte, and
the counter number are required for each configured counter. Word 0
must be used for each configured counter individually. Bit 10 is
ignored and bits 11, 13, and 14 must be zero. The values of words 1
through 7 are ignored by the module while in debug mode.
Figure 5.5 Required Bits for Min./Max. Count Value Block
15 14
13 12 11
10 09 08
07 06 05
04 03 02
01 00
Word 0
TRMT
0
0
DEBUG
0
0
0
0
BLOCK TYPE
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word 0
TRMT
0
0
DEBUG
0
0
0
0
BLOCK TYPE
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Word 0
TRMT
0
0
DEB
U
G
0
X
CNTR
No.
BLOCK TYPE
TIP
If the counter number entered is not valid, the
debug mode returns a programming error.