Configuration and Programming 4-5
Converting from Floating-Point to Two-word Integer Format
RSLogix500 programming software can also be used to convert from
floating-point to two-word integer format as shown.
0001
0002
0003
0004
Divide
Source A
F8:4
0.0
<
Source B
1000.0
1000.0
<
Dest
F8:3
0.0
<
Move
Source
F8:3
0.0
<
Dest
N7:34
0<
Grtr Than or Eql (A>=B)
Source A
F8:4
0.0
<
Source B
0.0
0.0
<
Greater Than (A>B)
Source A
N7:34
0<
Source B
F8:3
0.0
<
Subtract
Source A
N7:34
0<
Source B
1
1<
Dest
N7:34
0<
Compute
Dest
N7:35
0<
Expression F8:4 - ( N7:34 * 1000.0 )
Less Than (ASource A
F8:4
0.0
<
Source B
0.0
0.0
<
LES
Less Than (ASource A
N7:34
0<
Source B
F8:3
0.0
<
ADD
Add
Source A
N7:34
0<
Source B
1
1<
Dest
N7:34
0<
Compute
Dest
N7:35
0<
Expression F8:4 + ( ( - N7:34 ) * 1000.0 )
TWO-WORD 1 TEMP
TWO-WORD 1 MSW
FLOAT TO TWO-WORD
INT VALUE
FLOAT TO TWO-WORD
INT VALUE
TWO-WORD INT 1 MSW
TWO-WORD INT 1 MSW
TWO-WORD INT 1 MSW
TWO-WORD INT 1 MSW
TWO-WORD INT 1 LSW
TWO-WORD INT 1 LSW
LES
CPT
CPT
SUB
GRT
GEQ
DIV
MOV
F8:4 holds the number to be converted. It is divided by 1000 and the result is placed in F8:3.
The value in F8:3 is moved to N7:34, yielding the upper word
(Most Significant Word - MSW).
Rung 3 is used only when the original value in F8:4 is positive. If the value in N7:34 was rounded up, as determined
by comparing it to the floating point version in F8:3, the value must be adjusted by subtracting one from it. The
lower (Least Significant Word) - LSW) is then calculated by subtracting (MSW multiplied by 1000) from the original
value.
Rung 4 is used only when the original value in F8:4 is negative. If the value in N7:34 was rounded up, as determined
by comparing it to the floating point version in F8:3, the value must be adjusted by adding one to it. The lower
(LSW) is then calculated by adding (MSW multiplied by 1000) to the original value.