Publication 1746-UM003A-EN-P
Channel Configuration, Data, and Status 4-15
Table 4.13 Channel Data Word Resolution for 500
Ω
Ω
Ω
Ω
Platinum (385)
Table 4.14 Channel Data Word Resolution for 1000
Ω
Ω
Ω
Ω
Platinum (385)
Table 4.15 Channel Data Word Resolution for 500
Ω
Ω
Ω
Ω
Platinum (3916)
Table 4.16 Channel Data Word Resolution for 1000
Ω
Ω
Ω
Ω
Platinum (3916)
Table 4.17 Channel Data Word Resolution for 604
Ω
Ω
Ω
Ω
Nickel Iron (518)
Excitation Current
Data Format (Bits 4 and 5)
(1)
Engineering Units x 1
Engineering Units x
10
Scaled-for-PID
Proportional Counts
(Default)
°C
°F
°C
°F
°C
°F
°C
°F
0.25 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0641°C/step 0.1154°F/step 0.0160°C/step 0.0288°F/step
1.0 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0360°C/step 0.0648°F/step 0.0090°C/step 0.0162°F/step
(1)
Excitation Current
Data Format (Bits 4 and 5)
(1)
Engineering Units x 1
Engineering Units x
10
Scaled-for-PID
Proportional Counts
(Default)
°C
°F
°C
°F
°C
°F
°C
°F
0.25 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0641°C/step 0.1154°F/step 0.0160°C/step 0.0288°F/step
1.0 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0153°C/step 0.0275°F/step 0.0038°C/step 0.0069°F/step
(1)
Excitation Current
Data Format (Bits 4 and 5)
(1)
Engineering Units x 1
Engineering Units x
10
Scaled-for-PID
Proportional Counts
(Default)
°C
°F
°C
°F
°C
°F
°C
°F
0.25 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0507°C/step 0.0912°F/step 0.0127°C/step 0.0228°F/step
1.0 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0354°C/step 0.0637°F/step 0.0089°C/step 0.0159°F/step
(1)
Excitation Current
Data Format (Bits 4 and 5)
(1)
Engineering Units x 1
Engineering Units x
10
Scaled-for-PID
Proportional Counts
(Default)
°C
°F
°C
°F
°C
°F
°C
°F
0.25 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0507°C/step 0.0912°F/step 0.0127°C/step 0.0228°F/step
1.0 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0153°C/step 0.0275°F/step 0.0038°C/step 0.0104°F/step
(1)
Excitation Current
Data Format (Bits 4 and 5)
(1)
Engineering Units x 1
Engineering Units x
10
Scaled-for-PID
Proportional Counts
(Default)
°C
°F
°C
°F
°C
°F
°C
°F
0.25 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0183°C/step 0.0330°F/step 0.0046°C/step 0.0082°F/step
1.0 mA
0.1°C/step 0.1°F/step
1°C/step
1°F/step
0.0232°C/step 0.0417°F/step 0.0058°C/step 0.0104°F/step
(1)