Resistance device compatibility, Cable specifications, Rtd standards – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual
Page 105: Cable specifications rtd standards

Publication 1746-UM003A-EN-P
Specifications A-5
Resistance Device Compatibility
Table A.1 Resistance Input Specifications
Cable Specifications
RTD Standards
Input Type
Resistance Range
(0.25 mA Excitation)
Resistance Range
(1.0 mA Excitation)
Resolution
Repeatability
(28 Hz, 50/60 Hz)
Resistance
150
Ω
0 to 150
Ω
Ω
0.01
Ω
± 0.04
Ω
500
Ω
0 to 500
Ω
Ω
0.1
Ω
± 0.2
Ω
1000
Ω
0 to 1000
Ω
Ω
0.1
Ω
± 0.2
Ω
3000
Ω
0 to 3000
Ω
Ω
0.1
Ω
± 0.2
Ω
Description
Belden #9501
Belden #9533
Belden #83503
When used
For 2-wire RTDs and potentiometers. For 3-wire RTDs and potentiometers.
Short runs less than 100 feet and
normal humidity levels.
For 3-wire RTDs and potentiometers.
Long runs greater than 100 feet or
high humidity levels.
Conductors
2, #24 AWG tinned copper (7× 32)
3, #24 AWG tinned copper (7× 32)
3, #24 AWG tinned copper (7× 32)
Shield
Beldfoil aluminum polyester shield
with copper drain wire.
Beldfoil aluminum polyester shield
with copper drain wire.
Beldfoil aluminum polyester shield
with tinned braid shield.
Insulation
PVC
S-R PVC
Teflon
Jacket
Chrome PVC
Chrome PVC
Red teflon
Agency Approvals
NEC Type CM
NEC Type CM
NEC Art-800, Type CMP
Temperature Rating
80°C
80°C
200°C
RTD Type
α
αα
α
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
100
Ω
Platinum
0.00385
X
X
X
200
Ω
Platinum
0.00385
X
X
X
500
Ω
Platinum
0.00385
X
X
X
1000
Ω
Platinum
0.00385
X
X
X
100
Ω
Platinum
0.03916
X
X
200
Ω
Platinum
0.03916
X
X
500
Ω
Platinum
0.03916
X
X
1000
Ω
Platinum
0.03916
X
X
10
Ω
Copper
(9)
0.00426
X
120
Ω
Nickel
(10)
0.00618
X
120
Ω
Nickel
0.00672
X
604
Ω
Nickel Iron
0.00518
X
(1)
α
is the temperature coefficient of resistance which is defined as the resistance change per ohm per °C.
(2) International Electrotechnical Commission Standard 751-1983
(3) German Standard, DIN 43760-1980 and DIN 43760-1987
(4) U.S. Standard D100
(5) Scientific Apparatus Makers Association Standard RC21-4-1966
(6) Japanese Industrial Standard JIS C1604-1981
(7) Japanese Standard JIS C1604-1989
(8) Minco Type ‘NA’ (Nickel) and Minco Type ‘FA’ (Nickel-Iron)
(9) Actual value at 0°C is 9.042
Ω
per SAMA standard RC21-4-1966.
(10) Actual value at 0°C is 100
Ω
per DIN standard.
ATTENTION
!!!!
We recommend you use
RTDs that conform to the
standards in the table
above. Failure to heed this
caution may result in
reduced accuracy of the
RTD system.