Scaling examples, Scaled-for-pid to engineering units, Engineering units to scaled-for-pid – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual
Page 59

Publication 1746-UM003A-EN-P
Channel Configuration, Data, and Status 4-11
Scaling Examples
The following examples are using the default scaling ranges:
Scaled-for-PID to Engineering Units
Equation:
Assume that the input type is an RTD, Platinum (200
Ω
, a = 0.00385°C,
range = -200°C to +850°C), scaled-for-PID display type. Channel data = 3421.
Want to calculate °C equivalent.
From Channel Data Word Format, S
LOW
= -200°C and S
HIGH
= 850°C.
Solution:
Solution:
Solution:
Solution:
Engineering Units to Scaled-for-PID
Equation:
Assume that the input type is an RTD, Platinum (200
Ω
, a = 0.00385°C,
range = -200°C to +850°C), scaled-for-PID display type. Desired channel
temperature = 344°C.
Want to calculate Scaled-for-PID equivalent.
From Channel Data Word Format, S
LOW
= -200°C and SHIGH = 850°C.
Solution:
Engr Units Equivalent
SLOW
SHIGH - SLOW
(
)
Scaled-for-PID value displayed
16383
-------------------------------------------------------------------------------
×
+
=
Engr Units Equivalent
200°C
850°C - (-200°C)
(
)
3421
16383
---------------
×
19.25°C
=
+
=
Scaled-for-PID Equivalent
16383
Engr Units desired - SLOW
(
)
SHIGH - SLOW
(
)
--------------------------------------------------------------------------
×
=
Scaled-for-PID Equivalent
16383
344°C
-200°C
(
)
+
850°C- (-200°C)
-----------------------------------------------
Ч
8488
=
=