beautypg.com

System overview, System operation, System overview -7 – Rockwell Automation 1746-NR8 SLC 500 RTD/Resistance Input Module User Manual User Manual

Page 17: System operation -7

background image

Publication 1746-UM003A-EN-P

Overview 1-7

System Overview

Figure 1.3 RTD Configuration

Each individual channel on the RTD module can receive input signals from 2,
3 or 4-wire RTD sensors or from resistance input devices. You configure each
channel to accept either input. When configured for RTD input types, the
module converts the RTD readings into linearized, digital temperature
readings in °C or °F. When configured for resistance inputs, the module
provides a linear resistance value in ohms.

System Operation

The RTD module has 3 operational states:

power-up

module operation

error (module error and channel error)

IMPORTANT

The RTD module is designed to accept input from RTD
sensors with up to 3 wires. When using 4-wire RTD
sensors, one of the 2 lead compensation wires is not used
and the 4-wire sensor is treated like a 3-wire sensor. Lead
wire compensation is provided via the third wire. Refer
to Wiring Considerations on page 2-8 fo
r more
information.

RTD Modules

SLC Processor