6–10

Input, Output and Configuration Files for Analog Modules when used with ControlNet

Publication 1794ĆUM015B-EN-P - May 2001

Configuration

Word

Bit

Definition

Word 0

Channel 0 Control Word - Control word for setting the function of counter 0.

Bits 00-02

02 01 00

Mode Selection bits

0

0

0

Counting on positive (rising) edge of input signal A. (Up/dwn counting determined by B.)

0

0

1

Quadrature encoder X1

0

1

0

Quadrature encoder X2

0

1

1

Quadrature encoder X4

1

0

0

Counting up on the positive edge of input signal A, and down on positive edge of input

signal B.

1

0

1

No count function.

1

1

0

No count function.

1

1

1

No count function.

Bit 03

Preset (Reset) bit - A positive edge on this bit moves the value in Preset X to Counter X, independent of

Preset Enable. NOTE: To use Preset as Reset, use a count value of 0000 in the Preset value word.

Bit 04

Enable Z Preset bit - When this bit is set (1), a positive edge on Z preloads Counter X = Preset X,

independent of Cal Enable. NOTE: If Z is configured to do Store and Preset (Reset), the Store will occur

first.

Bit 05

Count Enable bit - When this is set (1), the pulse counter is enabled.

Bits 06-08

(06 10)

Calibration Control bits - bits 06, 07 and 08

(06-10)

06 Enable bit - When this bit is set (1), the counter can be calibrated.
07 Direction bit - When this bit set (1), calibration is performed in a negative direction; when reset (0),

calibration is performed in a positive direction.

08 Reset bit - Calibration is acknowledged and a new calibration is enabled on a positive edge on this

bit.

Bits 09-10

(11 12)

10 09 Gate Control bits

(11-12)

0

0

No gate function on input G

0

1

Counting only if G is high (active)

1

0

Counting only if G is low (inactive)

1

1

The counter can be calibrated when G is high (active).

Bits 11-12

(13-14)

12 11 Store Control bits - These bits will trigger a Store only if the channel Store status bit (L0 or L1)

is cleared (0).

0

0

Save the counter value on the positive edge of Z (if Latched X = 0)

0

1

Save the counter value on the positive edge of G (if Latched X = 0)

1

0

Save the counter value on the negative edge of G (if Latched X = 0)

1

1

Save the counter value on the positive edge and negative edge of G (if Latched X = 0)

Bit 13 (15)

Rollover bit - When set (1), the counter counts up to the preset and then restarts at 0. If this bit is reset (0)

(not rollover), the rollover preset value = FFFF (hex = 65535 (decimal).

Bit 14 (16)

Store Reset bit - A positive edge on this bit resets Store X in Signals.

Bit 15 (17)