Rockwell Automation 1794-ID2 U.MNL INCREMENTAL ENCODER User Manual
Page 69
6–7
Input, Output and Configuration Files for Analog Modules when used with ControlNet
Publication 1794ĆUM015B-EN-P - May 2001
Definition
Bit
InputWord
Bit 06
Status for input Z (pulse transmitter 1) - This bit, when set, indicates a signal at Z.
Bit 07
Status for input G (pulse transmitter 1) - This bit, when set, indicates a signal at G.
Bit 08 (10)
Cal 0 - This bit, when set (1), indicates that counter 0 has been calibrated. This bit is reset by CalReset.
Bit 09 (11)
Cal 1 - This bit, when set (1), indicates that counter 1 has been calibrated. This bit is reset by CalReset.
Bit 10 (12)
Store 0 - This bit, when set (1), indicates a counter value is saved in store 0. This bit is reset by StoreReset.
Word 0
continued
Bit 11 (13)
Store 1 - This bit, when set (1), indicates a counter value is saved in store 1. This bit is reset by StoreReset.
continued
Bit 12 (14)
PresetReached 0 (PR0) - When this bit is set (1), in all configuration modes, the counter 0 value equals the
preset 0 value, either in a positive or negative direction. This bit is reset by PresetReset0 and can only be set
again after at least 1 more pulse.
Bit 13 (15)
PresetReached 1 (PR0) - When this bit is set (1), in all configuration modes, the counter 1 value equals the
preset 1 value, either in a positive or negative direction. This bit is reset by PresetReset1 and can only be set
again after at least 1 more pulse.
Bit 14-15
(16-17)
Not used - set to 0
Word 1
Bits 00-15
(00-17)
Store 0 - Saved counter value on channel 0
Word 2
Bits 00-15
(00-17)
Store 1 - Saved counter value on channel 1
Word 3
Bits 00-15
(00-17)
Channel 0 CurrentCounter Value- Current value in counter 0
Word 4
Bits 00-15
(00-17)
Channel 1 CurrentCounter Value- Current value in counter 1
Word 5
Bits 00-15
(00-17)
Channel 0 Readback- Counter word readback)
Word 6
Bits 00-15
(00-17)
Channel 0 Readback- Counter word readback)
Word 7
Bits 00-15
(00-17)
Software identification