I/o module keying dip switch settings, Switch setting summary, Switch setting summary -22 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual
Page 76: Sw2 -22

Publication 1747-UM006B-EN-P - June 2003
4-22 Configuration
I/O Module Keying DIP Switch Settings
The 1747-ASB module is shipped from the factory with the default
position ON (save mode).
Switch Setting Summary
The following is a summary listing the various DIP switch settings.
IMPORTANT
Use save mode during setup and debug. After
debugging is complete, power up in save mode one
last time. Remove power and place the 1747-ASB
module in check mode prior to normal operation.
SW3
Save Mode
4
1
23
5
6
7
8
O
N
SW3
Check Mode
4
1
23
5
6
7
8
O
N
SW1
•
Logical Rack Number
For details, see page 4-2.
•
Logical Group Number
SW2
•
Baud Rate
•
Primary/Complementary Chassis
ON=Primary
OFF=Complementary (default)
•
1747-ASB Module Image Size
For details, see page 4-9.
1
O
N
24
5
6
7
8
3
SW1
Logical Rack Number Bit 5 (MSB)
Logical Rack Number Bit 4
Logical Rack Number Bit 3
Logical Rack Number Bit 2
Logical Rack Number Bit 1
Logical Rack Number Bit 0 (LSB)
Logical Group Number Bit 1 (MSB)
Logical Group Number Bit 0 (LSB)
7
8
Group
ON
ON
0 (default)
ON
OFF
2
OFF
ON
4
OFF
OFF
6
SW2
1
O
N
24
5
6
7
8
3
Baud Rate Bit 1 (MSB)
Baud Rate Bit 0 (LSB)
Primary/Complementary Chassis
Reserved
ASB Module Image Size Bit 3 (MSB)
ASB Module Image Size Bit 2
ASB Module Image Size Bit 1
ASB Module Image Size Bit 0 (LSB)