1747-asb module 2 configuration details -20 – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual
Page 124

Publication 1747-UM006B-EN-P - June 2003
8-20 Application Examples
1747-ASB Module 2 Configuration Details
Because the image of 1747-ASB module 2 does not cross a logical rack
boundary, 1747-ASB module 2 appears as one logical device to the
scanner.
1747-ASB module 2 is configured for last chassis because it has the
highest logical group (group 5) in its highest numbered logical rack
(logical rack 3).
1747-ASB module 2 is not configured for hold last state and processor
restart lockout. If the RIO communications cable is removed and
reconnected during normal RIO communications, the discrete outputs
are reset and the 1747-ASB module automatically resumes
communicating with the PLC-5/40.
1747-ASB module 2 is configured as a complementary chassis.
Because complementary I/O is not being used, there is no need for a
primary chassis.
The 1747-ASB module 2 response time is unrestricted because the
PLC-5/40 does not require a restricted response time.
PLC Processor Input Image
PLC Processor Output Image
Bit Number
Octal
0
7
10
17
Bit Number
Octal
0
7
10
17
Logical
Rack 3
I:030
I:031
I:032
I:033
I:034
I:035
I:036
I:037
Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
Logical
Rack 3
O:030
O:031
O:032
O:033
O:034
O:035
O:036
O:037
Group 0
Group 1
Group 2
Group 3
Group 4
Group 5
Group 6
Group 7
1747-ASB
Module 2
Not Used
Not Used
NO4I
NO4I
NO4I
NO4I
NO4I
NO4I
NO4I
NO4I
1747-ASB
Module 2
Not Used
Not Used
NIO4I
NIO4I
NIO4I
NIO4I
NIO4I
NIO4I
NIO4I
NIO4I
NI4
NI4
NI4
NI4
NI4
NI4
NI4
NI4