Rockwell Automation 1771-DE Absolute Encoder Module User Manual User Manual

Page 46

background image

Appendix A

AĆ5

1.

Calculate the system values that are determined by the system
configuration.

Program Scan (PS) = (5 ms/1K words) x (number of program

words)

Processor I/O Scan (PIO) = (1 ms/rack number) x (number of

declared rack numbers)

Number of words transferred (W) = 2 (read) or 20 (write)

2.

Calculate the block-transfer time (T) for the read or write operation.

T

= 0.08 ms/word x number of words transferred

3.

Calculate the worst case system time (ST) between transfers.

ST

=PS + PIO + T(1)(read) + T(2)(read) +T(3)(read) +...
PS + PIO + T(1)(write) + T(2)(write) + T(3)(write) +...

=2(PS + PIO) + T(1)(read) + T(2)(read) + T(3)(read) + ...
T(1)(write) + T(2)(write) + T(3)(write) + ...

Example 2

A PLC-2/30 programmable controller is controlling four I/O racks
in a local configuration. Assume one block-transfer module per
chassis and one assigned rack number per chassis (Figure A.2).