beautypg.com

Rockwell Automation 1771-DE Absolute Encoder Module User Manual User Manual

Page 20

background image

Configuring and Installing Your Module

Chapter 3

3Ć8

We recommend the following Belden cable or its equivalent to connect
the encoder to the module (maximum 50 feet). Use extra twisted pairs to
connect power to the encoder.

No. of

No. of Twisted

Belden Cable No.

Encoder Bits

Pairs in Cable

18 AWG

20 AWG

8

9

9775

9875

10

11

Ć

9876

Ć

12

9776

9877

12

15

9777

9879

Important: Tighten wiring arm connections to 9 inch-pounds of torque.

WARNING: Do not remove the wiring-arm from an

operating module; it will cause the power-up bit status to
change unpredictably until a valid write to the module occurs.

If swing-arm power is lost, turn on the power-up bit and disable
all outputs until a valid write occurs.

Connecting a SingleĆended Output Encoder

Us

e Figure 3.6

to connect a single-ended output encoder. Connect the

signal line for bit 0 to terminal 1 of the left wiring arm. Connect its return
to terminal 2. Connect bit 1 signal line to terminal 3 and its return to
terminal 4. Continue in this way for all encoder channels.

If the encoder has less than 12 signal bits, jumper the unused input
terminals. For example, if you are using a 10-bit encoder, jumper
terminals 19 and 20 and terminals 17 and 18 on the right wiring arm.

WiringĆArm Connections