beautypg.com

Configuring and installing your module chapter 3 – Rockwell Automation 1771-DE Absolute Encoder Module User Manual User Manual

Page 19

background image

Configuring and Installing Your Module

Chapter 3

3Ć7

Output Power Supply

To power the eight outputs (Figure 3.5), connect at least one +5 to +24V
DC supply to terminal 1 and terminal 6 (or 7) of the right wiring arm.
You can connect another +5 to +24V DC power supply between terminals
9 and 14 (or 15) of the right wiring arm if, for example, you need two
different load supply voltages.

If you need only one supply voltage, connect a wire between terminals 1
and 9 and connect another wire between terminal 6 (or 7) and terminal 14
(or 15).

Figure 3.5

Connection Diagram for Output Devices

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

Output Supply (+5 to 24V dc)
Output 0
Output 1
Output 2
Output 3
Output Common (+5 to 24V dc)
Output Common (+5 to 24V dc)
Not Used
Output Supply (+5 to 24V dc)
Output 4
Output 5
Output 6
Output 7
Output Common (+5 to 24V dc)
Output Common (+5 to 24V dc)
Not Used
Bit 10
Bit 10 / Common
Bit 11
Bit 11 / Common
Input Common (+5V dc)

12838

Right

Wiring

Arm

For Outputs

0 - 3

For Outputs

4 - 7

+5 to 24V

DC User

Supply

+

-

+

-

+5 to 24V

DC User

Supply

+

-

+

-

DC Output

Devices

Input circuitry

Tie Wires

Here

(See Applicable