66 Configure Modules in RSLogix 5000 Software
Calibration Dialog
To complete the entries on the Calibration Dialog, proceed as follows. Module
must be inhibited before you can begin calibration.
1. Click Calibration to display the dialog.
2. Check the Calibrate checkbox to specify channels to calibrate.
3. For Type of Calibration, select one of the following:
• Input
• Cold Junction
Disable All
Alarms
Click to check the
checkbox
A check in the checkbox indicates that the
alarm is disabled.
An attempt to write a non-valid (any Spare
value) into the I/O Disable all Alarms field
will cause a profile validation error. If the
alarm is disabled, the whole line for the
channel can be disabled for alarms. Disable
in Hard Run Mode only.
Unlatch
Click the push button
next to the alarm
Click the Unlatch button to unlatch each
alarm individually.
This feature is disabled when offline and in
Hard Run mode.
Latch Process
Alarms
Click to check the
checkbox
Click to unlatch all alarms together.
This feature is disabled when offline and in
Hard Run mode.
IMPORTANT
Configure channels that will be calibrated to MV Sensor Type
and apply.
For This Value
Select
Comments