Add i/o modules to your network pointbus – Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual
Page 30
![background image](/manuals/579406/30/background.png)
Publication 1734-UM004F-EN-E - December 2012
20 Configure Your Module
This chapter shows configuration in the online mode. Configuration dialogs
appear similar in both modes. The primary difference is that if you make
changes offline, you must go online before the configuration changes take
effect.
Perform this procedure to add a communication device.
1. Start the RSNetWorx for DeviceNet software.
2. Add the communication adapter as shown in the figure.
In this case, the chosen device was a 1770-KFD RS232 Interface.
Add I/O Modules to Your Network POINTBus
After you add the communication device, you must add the POINT I/O
modules connected to the scanner on the POINTBus.
Add modules as shown in the figure.
1. Click here to expand the list of
communication adapters.
2. Double-click here to choose the
scanner. You can also click and
drag the scanner name onto
the network.
Make sure you choose the
1734-ADN POINT I/O Scanner.
The scanner appears
on the network.
1. Click here to expand the list of
Specialty modules.
2. Double-click the catalog number
to choose the module. You can
also click and drag the module
name onto the network.