4 - calibrate your module, Overview, When and how to calibrate your module – Rockwell Automation 1734-IT2I Thermocouple and RTD Input Module User Manual User Manual
Page 49: Calibration method, Chapter 4, Calibrate your module, Chapter
39
Publication 1734-UM004F-EN-E - December 2012
Chapter
4
Calibrate Your Module
Overview
Use this chapter to calibrate the thermocouple/mV module or the RTD input
module. Refer to the table for a summary of what is covered.
When and How to Calibrate
Your Module
Your module is shipped to you already calibrated. If a calibration check is
required, the module must be in a POINT I/O system.
Perform module calibration periodically, based on your application. Module
calibration may also be required to remove module error due to aging of
components in your system.
Calibration Method
Perform calibration through the I/O configuration software, such as
RSNetWorx and EDS files. If the EDS files are not in your software, get them
online at
.
Tools and Equipment
Required to Calibrate
Your Thermocouple Module
To calibrate your thermocouple module, you need the following tools and
equipment.
Task
Page
When and How to Calibrate Your Module
Tools and Equipment Required to Calibrate Your Thermocouple Module
Calibrate the Thermocouple Input Module
Cold Junction Compensation Calibration
Tools and Equipment Required to Calibrate Your RTD Module
Calibrate the RTD Input Module
Tool or Equipment
Description
Precision Resistors
High precision resistors:
1000
Ω
, 0.05%, 5 ppm/
o
C
3000
Ω
, 0.05%, 5 ppm/
o
C
or
Calibrated resistor Decade Box, 0.05%
Precision Voltage Source
+100 mV, 1 mV resolution - accuracy +3
μ
V or better