Rockwell Automation 1738-AENT, Series B ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual
Page 88

76
Rockwell Automation Publication 1738-UM005A-EN-P - July 2013
Chapter 6 Troubleshoot the Adapter
Status Indicators for 1738-AENT/B Adapter
Indicator
Status
Description
Adapter Status
Off
No power applied to device
Flashing green
Device needs commissioning due to missing, incomplete, or incorrect configuration.
Solid green
Device operating normally
Flashing red
Recoverable fault.
Complete firmware update, verify address switches.
Solid red
Unrecoverable fault has occurred:
• self test failure (checksum failure at power cycle, ramtest) at power cycle.
• firmware fatal error.
Flashing red/green
Module self-test
Network Activity
Off
No Link established.
Flashing green/Off
Transmit or receive activity present.
Solid green
Link established.
Network Status
Off
Device not initialized. The module does not have an IP address.
Flashing green
No CIP connections present. Device has an IP address, but no CIP
connections are established.
Solid green
CIP connections present. Device online and has an IP address, and CIP
connections are established.
Flashing red
One or more CIP connections in timed-out state. Check for I/O module failure
and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing red/green
The module is performing a self-test (only occurs during cycle
power test).
POINTBus Status
Off
Device not powered – check module status indicator.
Flashing red/green
LED cycle power test present.
Flashing red
Recoverable fault occurred:
• At cycle power, the number of expected modules does not equal the number of modules
present.
• A module is missing.
• Node fault (I/O connection timeout) occurred.
Solid red
Unrecoverable fault occurred – the adapter is bus off.
Flashing green
Firmware (NVS) update in progress.
Solid green
Adapter online with connections established (normal operation,
Run mode).
System Power
Off
Not active; field power is off or DC-DC converter problem present.
Solid green
System power is on; DC-DC converter is active (5V).
Field Power
Off
Not active; field power is off.
Solid green
Power is on; 24V is present.