beautypg.com

Rockwell Automation 1738-AENT, Series B ArmorPOINT I/O Dual Port EtherNet/IP Adapters User Manual User Manual

Page 67

background image

Rockwell Automation Publication 1738-UM005A-EN-P - July 2013

57

Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software Chapter 5

Add the ArmorPOINT I/O
Adapter to the I/O
Configuration

Next, you must add the 1738-AENT/B adapter as a child of the local
1756-ENBT bridge module.

1. In the Project dialog, right-click the local 1756-ENBT bridge module

under the I/O Configuration folder and select New Module from the
dialog.

2. The Select Module Type dialog opens.

Select the appropriate Module Type filter Category (for the example we
selected Communication), and Module Type Vendor (for the example we
selected Allen-Bradley).

Note: to select only one category you will need to unselect those already
selected.

TIP

In the Select Module Type dialog, you have options to search for a
specific module, add modules to a Favorites list, filter by Category
and/or Vendor, Hide and Show Filters, use Module Discovery, sort by
vendor, or access your Favorites list.