Chapter 5 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Set Up the Hardware
The following section describe how to set up the I/O Hardware.
Set Up the ArmorPOINT I/O Hardware
In this example, a ControlLogix chassis contains the L63 controller in slot 1 and a
1756-ENBT bridge module in slot 3.
In this example, we mounted the 1738-AENT/B adapter on a DIN rail in slot 0,
with a 1738-OW2/C relay output module in slot 1, a 1738-OV4E/C sink
output module in slot 3, and two other ArmorPOINT I/O modules which will
not be controlled by this Logix controller in slots 2 and 4.
To work along with this example, set up your system as shown in the figure.
•
Note that in the example application, the Logix controller and
1756-ENBT module (firmware revision 2.3 or later) are assumed to be in
the slots shown above.
•
Verify the IP addresses for your programming terminal, 1756-ENBT
bridge module, and 1738-AENT/B adapter.
•
Verify the position (slot) of the I/O modules.
•
Verify that all wiring and cabling is properly connected.
•
Make sure your communication driver (for example, AB_ETH-1 or AB-
ETHIP-1) is configured in RSLinx software.
Ethernet Communication Driver on page 99
.
0
0
1
2
3
1
MOD
NET
1738-OB4EM12
24V dc Out
1738-AENT
Adapter
Status
Network
Activity
PointBus
Status
System
Power
Adapter
Power
EtherNet I/P
PWR
x1
x10
6
0
8
2
4
6
0
8
2
4
0
0
2
1
2
3
1
3
MOD
NET
1738-IB4M12
24V dc In
I
x100
6
0
8
2
4
Network
Status
conformance tested
™
P
A
E
D
D
R
S
S
0
0
2
1
MOD
NET
1738-OE2CM12
Analog Current Out
0
0
1
1
MOD
NET
1738-IE2CM12
Analog Current In
2
3
Local Chassis
ArmorPOINT I/O
L63
Controller (slot 1)
1756-ENBT
10.88.70.90 (slot 3)
Data
Switch
10.88.70.26
Programming
Terminal
Slot 0 1 2 3
1738-AENT/B
10.88.70.2
45176