Rockwell Automation 1395 DC Drive, 800-1250 Hp, FRN 5.XX-9.30 User Manual
Page 135

Chapter 5
Programming Parameters
5-44
Parameter 644 – Mop Accel 4 [Mop Accel 4]
Internal units : Seconds x 10
Programming Terminal units: Seconds
Minimum Value: 0.1
Maximum Value: 6553.5
Default Value: 0.1
Description: This parameter determines the acceleration rate of the
MOP generated velocity reference when Mop rate 4 has been selected
in the logic command word. The units are in seconds to accelerate
from 0 to base speed.
Parameter 645 – Mop Decel 1 [Mop Decel 1]
Internal units : Seconds x 10
Programming Terminal units: Seconds
Minimum Value: 0.1
Maximum Value: 6553.5
Default Value: 0.1
Description: This parameter determines the deceleration rate of the
MOP generated velocity reference when Mop rate 1 has been selected
in the logic command word. The units are in seconds to decelerate
from base speed to zero speed.
Parameter 646 – Mop Decel 2 [Mop Decel 2]
Internal units : Seconds x 10
Programming Terminal units: Seconds
Minimum Value: 0.1
Maximum Value: 6553.5
Default Value: 0.1
Description: This parameter determines the deceleration rate of the
MOP generated velocity reference when Mop rate 2 has been selected
in the logic command word. The units are in seconds to decelerate
from base speed to zero speed.
Parameter 647 – Mop Decel 3 [Mop Decel 3]
Internal units : Seconds x 10
Programming Terminal units: Seconds
Minimum Value: 0.1
Maximum Value: 6553.5
Default Value: 0.1
Description: This parameter determines the deceleration rate of the
MOP generated velocity reference when Mop rate 3 has been selected
in the logic command word. The units are in seconds to decelerate
from base speed to zero speed.