Chapter 5
Programming Parameters
5-32
Parameter 166 – Velocity Indirect 4 [Vel Indirect 4]Veloc
Internal units :
Programming Terminal units :
Description : This is the Fast Sink, with its pointer in Parameter 603,
Velocity Parameter Select 4.
Parameter 167 – Torque Reference 2 [Torque Ref 2]
Internal units : 4096 = 100% Rated Motor Torque
Programming Terminal units : Percent Rated Motor Torque
Minimum Value: NA
Maximum Value: NA
Default Value: 0
Function: Torque Control
Description : This is a Parameter Sink that can be used to bring a
second Torque Reference into the Drive. The data that is linked to
this parameter is scaled using the Slave % 2 parameter and then
summed with the Torque Reference value from Parameter #157.
Parameter 600 – Velocity Parameter 1 Select [Vel Param 1 Sel]
Internal units : RPM
Programming Terminal units: RPM
Minimum Value: 600
Maximum Value: 732
Default Value: 600
Description : This is the pointer for Parameter 163 Velocity Indirect 1
Parameter 601 – Velocity Parameter 2 Select [Vel Param 2 Sel]
Internal units : RPM
Programming Terminal units: RPM
Minimum Value: 600
Maximum Value: 732
Default Value: 601
Description : This is the pointer for Parameter 164 Velocity Indirect 2
Parameter 602 – Velocity Parameter 3 Select [Vel Param 3 Sel]
Internal units : RPM
Programming Terminal units: RPM
Minimum Value: 600
Maximum Value: 732
Default Value: 602
Description : This is the pointer for Parameter 165 Velocity Indirect 3
Parameter 603 – Velocity Parameter 4 Select [Vel Param 4 Sel]
Internal units : RPM
Programming Terminal units: RPM
Minimum Value: 600
Maximum Value: 732
Default Value: 603
Description : This is the pointer for Parameter 166 Velocity Indirect 4