beautypg.com

Rockwell Automation 1395 DC Drive, 800-1250 Hp, FRN 5.XX-9.30 User Manual

Page 109

background image

Chapter 5
Programming Parameters

5-18

At speed 3 (Bit 13) : A 1-bit field that is set to 1 when the actual
velocity of the motor is greater than the at speed 3 setpoint.
Otherwise, set to 0. Internally in the drive, if the feedback velocity
(Parameter 106) is greater than or equal to at speed 3 (Parameter
706), the at speed 3 bit is set to 1.

At speed 4 (Bit 14) : A 1-bit field that is set to 1 when the actual
velocity of the motor is greater than the at speed 4 setpoint.
Otherwise, set to 0. Internally in the drive, if the feedback velocity
(Parameter 106) is greater than or equal to at speed 4 (Parameter
707), the at speed 4 bit is set to 1.

At speed 5 (Bit 15) : A 1-bit field that is set to 1 when the actual
velocity of the motor is greater than the at speed 5 setpoint.
Otherwise, set to 0. Internally in the drive, if the feedback velocity
(Parameter 106) is greater than or equal to at speed 5 (Parameter
708), the at speed 5 bit is set to 1.

Parameter 101 – Drive Fault [Drive Fault]

Internal units : None
DHT units : Bit field
Description : A status word maintained by the Drive stating a fault is
true (bit set to 1) or false (bit set to 0). Fault Report (Parameter 630)
determines if Velocity Control faults will be reported (630 = 1) or if
Current Control faults will be reported (630 = 0). Bit 15 is a status bit
that indicates which control faults are being reported. If bit 15 = 1,
velocity control faults are being reported. If bit 15 = 0, current
control faults are being reported. The bits in the drive fault word are
defined as: