Node address basics, Set the node address, Using the hardware mechanism – Rockwell Automation 193-DNENCATR EtherNet/IP Communications Auxiliary User Manual User Manual
Page 36
36
Rockwell Automation Publication 193-UM014B-EN-P December 2011
Chapter 4
Node Address Basics
• Verify the node address assigned to the new device.
• Prevent duplicate node address assignments.
– When connecting new DeviceNet modules with the Node
Commissioning tool from the EtherNet/IP Communications Auxiliary
web interface, place one new DeviceNet module on the network at a
time. Refer to “New DeviceNet Module” in
.
– If DIP or selector switches on hardware will be used, set the network
node address for the device before connecting it to the network.
• Leave node address 63 open.
For more information about setting the node address for DeviceNet devices, refer
to the Rockwell Automation Literature Library at:
www.rockwellautomation.com/literature
Set the Node Address
Using the Hardware Mechanism
Many DeviceNet devices feature a hardware mechanism to set the network node
address (e.g., a rotary switch or a push wheel switch). Use the following procedure
to set the node address.
1.
as a guide, select a node address to apply to the
new device.
IMPORTANT
Ensure each device’s node address set by the hardware mechanism
matches the node address used in the DeviceNet network. Note that if
the network node address is set higher than 63, the Ethernet /IP
Communications Auxiliary Node Commissioning tool can be used instead
of the hardware mechanism.
IMPORTANT
In order for the node address change to take effect, cycle the module’s
power.