Rockwell Automation 193-DNENCATR EtherNet/IP Communications Auxiliary User Manual User Manual

Page 32

background image

32

Rockwell Automation Publication 193-UM014B-EN-P December 2011

Chapter 3

3.

Type the size of the Scan List I/O Entry in the field.

The entry size determines the number of input and output bytes that the
EtherNet/IP Communications Auxiliary will scan from each of the
scanned devices. The maximum Scan List I/O Entry Size supported is 50
bytes with the default value being 8 bytes.

4.

If necessary, adjust DNet IO Request Packet Interval (RPI) and DNet IO
Inhibit.

DNet IO RPI determines the time it takes for data to be requested; DNet
IO Inhibit is the time used on DeviceNet Change of State (COS) I/O.
Both of these parameters are measured in milliseconds.

5.

Navigate to Scan List>Configuration>Scan List to change the DeviceNet
node address of the EtherNet/IP Communcations Auxiliary.

NOTE:

Auto Device Replacement (ADR) is discussed in

Chapter 6

,

Automatic Device

Recovery or Replace

.

NOTE:

Electronic keying is implemented on all scan list entries. Electronic keys are

captured when a scan list is configured form the EtherNet/IP Communications

Auxiliary webpage. The proper setting of the electronic keying becomes more

important with ADR functions and replacing units in the network.