Rockwell Automation 20-750-DNET PowerFlex DeviceNet Option Module User Manual
Page 87
![background image](/manuals/577768/87/background.png)
Rockwell Automation Publication 750COM-UM002B-EN-P - October 2012
87
Troubleshooting
Chapter 7
14
DPI Baud 500kbps
The option module detected that the drive was communicating at 500 Kbps.
15
DPI Host Invalid
The option module was connected to an incompatible product.
16
DPI Dup Port
Another peripheral with the same port number is already in use.
17
DPI Type 0 Logon
The option module has logged in for Type 0 control.
18
DPI Type 0 Time
The option module has not received a Type 0 status message within the specified time.
19
DPI DL Logon
The option module has logged into a Datalink.
20
DPI DL Error
The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another peripheral.
21
DPI DL Time
The option module has not received a Datalink message within the specified time.
22
DPI Ctrl Disable
The option module has sent a ‘Soft Control Disable’ command to the drive.
23
DPI Ctrl Enable
The option module has sent a ‘Soft Control Enable’ command to the drive.
24
DPI Msg Timeout
A Client-Server message sent by the option module was not completed within 1 second.
25
DPI Manual Reset
The option module was reset by changing its Reset Module parameter.
SI Events
26
SI Online
The option module has logged into the Serial Interface Communication.
27
SI Logon Error
The option module failed to log into the Serial Interface.
28
SI Comm Fault
The Serial Interface Communication has faulted.
Network Events
29
Net Link Up
A network link was available for the option module.
30
Net Link Down
The network link was removed from the option module.
31
Net Dup Address
The option module uses the same address as another device on the network.
32
Net Comm Fault
The option module detected a communication fault on the network.
33
Net Sent Reset
The option module received a reset from the network.
34
Net IO Close
An I/O connection from the network to the option module was closed.
35
Net Idle Fault
The option module received ‘idle’ packets from the network.
36
Net IO Open
An I/O connection from the network to the option module has been opened.
37
Net IO Timeout
An I/O connection from the network to the option module has timed out.
38
Net IO Size Err
The option module received an incorrectly sized I/O packet.
39
PCCC IO Close
The device sending PCCC Control messages to the option module has set the PCCC Control Timeout to zero.
40
PCCC IO Open
The option module has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a non-zero value).
41
PCCC IO Timeout
The option module has not received a PCCC Control message for longer than the PCCC Control Timeout.
42
Msg Ctrl Open
The timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing control messages to be sent to the
option module.
43
Msg Ctrl Close
The timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing control messages to be sent to the
option module.
44
Msg Ctrl Timeout
The timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.
45-46
Reserved
—
47
Net Bus Off
The network has experienced a Bus Off condition.
48
Net Poll Timeout
A Polled I/O connection has timed out.
49
Net IO Frag Err
A network I/O fragment was received out of sequence. Possible line noise problem.
50
Net COS Timeout
A Change of State (COS) connection has timed out.
Table 12 - Option Module Events (Continued)
Code
Event
Description