51

Configuring the I/O

Chapter 4

2.

Click Download to download the configuration to the controller.

When the download is successfully completed, RSLogix 5000 software
goes into the Online mode and the I/O OK box in the upper-left of the
dialog box should be steady green.

3.

From the File menu, choose Save.

If this is the first time you saved the project, the Save As dialog box appears.
a. Navigate to a folder.
b. Type a file name.
c. Click Save to save the configuration as a file on your computer.

4.

To ensure that the present project configuration values are saved, RSLogix
5000 software prompts you to upload them. Click Yes to upload and save.

5.

Place the controller in Remote Run or Run Mode.

TIP

If a message box reports that RSLogix 5000 software is unable to go
online, find your controller in the Who Active dialog box. From the
Communications menu, choose Who Active. After finding and
selecting the controller, click Set Project Path to establish the path. If
your controller does not appear, you need to add or configure the
DeviceNet driver with RSLinx software. See

Using RSLinx Classic

Software on page 37

and RSLinx online help for details.