Setting the node address, Using the powerflex 20-him-a6 or 20-him-c6s him to, Access parameters – Rockwell Automation 20-750-DNET PowerFlex DeviceNet Option Module User Manual
Page 26

26
Rockwell Automation Publication 750COM-UM002B-EN-P - October 2012
Chapter 3
Configuring the Option Module
Using the PowerFlex 20-HIM-
A6 or 20-HIM-C6S HIM to
Access Parameters
If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it
can be used to access parameters in the option module.
1.
Display the Status screen, which is shown on HIM powerup.
2.
Use the
or
key to scroll to the Port in which the option
module is installed.
3.
Press the PAR#
soft key to display the Jump to Param # entry pop-up box.
4.
Use the numeric keys to enter the desired parameter number, or use the
or
soft key to scroll to the desired parameter number.
For details on viewing and editing parameters, see the PowerFlex 20-HIM-A6/-
C6S HIM (Human Interface Module) User Manual, publicat
.
Setting the Node Address
When the option module Data Rate switch (
) is set to position ‘3’
(Program), the value of
Device Parameter 07 - [Net Addr Cfg] determines the
node address. When the Data Rate switch is set to any other position, the Node
Address switch settings determine the node address.
1.
Set the value of
Device Parameter 07 - [Net Addr Cfg] to a unique node
address.
2.
Reset the option module; see
Resetting the Option Module on page 32
.
The NET A status indicator will be steady green or flashing green if the
node address is correctly configured, and the option module is connected
to an operational network.
TIP
We recommend that you do not use node address 63 because all new devices
on the network use this address as the default address. Also, node address 63 is
used for Automatic Device Recovery (ADR).
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
Edit Net Addr Cfg
63
0 << 63