beautypg.com

Identity object, Class code, Services – Rockwell Automation 20-750-DNET PowerFlex DeviceNet Option Module User Manual

Page 100: Instances, Class attributes, Instance attributes

background image

100

Rockwell Automation Publication 750COM-UM002B-EN-P - October 2012

Appendix C

DeviceNet Objects

Identity Object

Class Code

Services

Instances

The number of instances depends on the number of components in the device
connected to the option module. This number of components can be read in
Instance 0, Attribute 2.

Class Attributes

Instance Attributes

Hexadecimal

Decimal

0x01

1

Service Code

Implemented for:

Service Name

Class

Instance

0x05

Yes

Yes

Reset

0x0E

Yes

Yes

Get_Attribute_Single

Instance

Description

0

Class

1

Host

2…15

Peripherals on Ports 1…14

Attribute ID

Access Rule

Name

Data Type

Description

2

Get

Max Instance

UINT

Total number of instances

Attribute ID

Access Rule

Name

Data Type

Description

1

Get

Vendor ID

UINT

1 = Allen-Bradley

2

Get

Device Type

UINT

141 = PowerFlex 750-Series via DeviceNet

3

Get

Product Code

UINT

Number identifying product name and rating

4

Get

Revision:

Major
Minor

STRUCT of:

USINT
USINT

Value varies
Value varies

5

Get

Status

UINT

Bit 0 = Owned
Bit 8 = Minor recoverable fault
Bit 10 = Major recoverable fault

6

Get

Serial Number

UDINT

Unique 32-bit number

7

Get

Product Name

SHORT_STRING

Product name and rating