Standard object types supported – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual
Page 75
Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
75
BACnet Protocol Implementation Conformance Statement Appendix D
Standard Object Types
Supported
The table below lists the object types supported by the Option Module. Dynamic
object creation and deletion is not supported. The property access rules use the
following key:
R = Read Only; the property is supported for this object type
W = Read/Write; the property is supported for this object type
C = Commandable; the property is supported for this object type
Property
Analog
Input
Analog
Output
Analog
Value
Binary
Input
Binary
Output
Binary
Value
Device
APDU Timeout
R
Application Software Version
R
Database Revision
R
Description
Device Address Binding
R
Event State
R
R
R
R
R
R
Firmware Revision
R
Location
Max APDU Length Accepted
R
Max Info Frames
Max Master
Model Name
R
Number of APDU Retries
R
Object Identifier
R
R
R
R
R
R
R
Object List
R
Object Name
R
R
R
R
R
R
W
(2)
Object Type
R
R
R
R
R
R
R
Out of Service
W
W
W
W
W
W
Polarity
R
R
R
Present Value
W
(1)
C
W
(1)
W
(1)
C
W
(1)
Priority Array
R
R
Protocol Object Types Supported
R
Protocol Revision
R
Protocol Services Supported
R
Protocol Version
R
Relinquish Default
R
R
Segmentation Supported
R
Status Flags
R
R
R
R
R
R
System Status
Units
R
R
R
Vendor Identifier
R
Vendor Name
R
(1) This property is writable when Out of Service is enabled.
(2) This property will accept a maximum of 20 characters when written.