Supported bacnet objects – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual
Page 40

40
Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter 4 Using BACnet Services and Objects
Supported BACnet Objects
The type of drive used on the network determines the specific BACnet objects
that are supported. See
for descriptions of the BACnet objects and the
drives supporting those objects.
Table 3 - BACnet Object Descriptions and Supported Drives
Object
Name
Use this Object to...
Drive
Parameter
Number
PowerFlex 750-
Series Drive
753
755
Analog Input (AI) Objects
AI0
Analog Input 1 (%)
Read the value of Analog Input 1 (voltage or current) on the drive’s I/O
terminal block.
260
✔
—
Analog Output (AO) Objects
AO0
Analog Output 1 (%)
Read/write the value of Analog Output on the drive’s I/O terminal block.
276
✔
—
Analog Value (AV) Objects
AV0
Speed Reference A
Read/write the Speed Reference A.
—
✔
✔
AV1
Speed Reference B
Read/write the Speed Reference B.
—
✔
✔
AV2
Output Frequency (Hz)
Read the drive’s output frequency.
1
✔
✔
AV3
Output Current (Amps)
Read the drive’s output current.
7
✔
✔
AV4
Output Voltage (VAC)
Read the drive’s output voltage.
8
✔
✔
AV5
Output Power (kW)
Read the drive’s output power.
9
✔
✔
AV6
Output Energy (kWh)
Read/write the drive’s accumulated output energy.
Important: When writing, this object accepts only a value of ‘0’ (zero).
14
✔
✔
✔
✔
AV7
Output Energy 2 (MWh)
Read/write the drive’s accumulated Output energy in terms of MWh.
Important: When writing, this object accepts only a value of ‘0’ (zero).
13
✔
✔
AV8
DC Bus Voltage (VDC)
Read the drive’s DC bus voltage.
11
✔
✔
AV9
Drive Temp (°C)
Read the drive’s temperature.
944
✔
✔
AV10
Reserved
—
—
—
—
AV11
Run Time (Hours)
Read/write the drive’s accumulated run time.
Important: When writing, this object accepts only a value of ‘0’ (zero).
15
✔
✔
✔
✔
AV12
Fault 1
Read the code for the drive’s most recent fault.
DPI Fault
Object
✔
✔
AV13
Fault 2
Read the code for the drive’s second most recent fault.
DPI Fault
Object
✔
✔
AV14
Fault 3
Read the code for the drive’s third most recent fault.
DPI Fault
Object
✔
✔
AV15
Accel Time 1 (Sec)
Read/write the drive’s Accel Time 1 setting.
535
✔
✔
AV16
Accel Time 2 (Sec)
Read/write the drive’s Accel Time 2 setting.
536
✔
✔
AV17
Decel Time 1 (Sec)
Read/write the drive’s Decel Time 1 setting.
537
✔
✔
AV18
Decel Time 2 (Sec)
Read/write the drive’s Decel Time 2 setting.
538
✔
✔
AV19
Reference 1 (%)
Read/write the Reference 1.
545
✔
✔
AV20
Reference 2 (%)
Read/write the Reference 2.
550
✔
✔