Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual
Page 68
![background image](/manuals/577758/68/background.png)
68
Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Appendix B
Option Module Parameters
16
[DHCP]
Enables/disables the Dynamic Host Configuration
Protocol server for setting the IP address of the
option module.
Default:
0 = Disabled
Values:
0 = Disabled
1 = Enabled
Type:
Read/Write
Reset Required: Yes
17
[Comm Loss Time]
Sets the communication loss timeout period in
seconds. The value zero (0) disables this function.
Default:
10 seconds
Minimum:
0 seconds
Maximum:
180 seconds
Type:
Read/Write
Reset Required: No
18
[Device Instnc]
Sets the Device Instance number used by the
option module on the BACnet network.
Default:
100
Minimum:
0
Maximum:
65535
Type:
Read/Write
Reset Required: Yes
19
[Device Port]
Sets the network node Device Port for the option
module to enable BACnet messaging to be sent
and received over the BACnet/IP network.
Default:
47808
Minimum:
0
Maximum:
60000
Type:
Read/Write
Reset Required: Yes
20
[BBMD Port Number]
Sets the Port number for BACnet Broadcast
Management Device connection.
Default:
47808
Minimum:
0
Maximum:
60000
Type:
Read/Write
Reset Required: Yes
21
22
23
24
[BBMD Cfg 1]
[BBMD Cfg 2]
[BBMD Cfg 3]
[BBMD Cfg 4]
Sets the bytes in the IP Address of the BACnet
Broadcast Management Device.
Default:
0
Default:
0
Default:
0
Default:
0
Minimum:
0
Maximum:
255
Type:
Read/Write
Reset Required: Yes
Parameter
No. Name and Description
Details
ATTENTION: Risk of injury or equipment damage exists. Device
Parameter 17 - [Comm Loss Time] lets you determine how long it will
take the option module to detect a network communication loss. By
default, this parameter sets the timeout to ten (10) seconds. You can set
it so that the duration is shorter, longer, or disabled. When set to
disabled, this also disables Host Parameter 33 - [Comm Flt Action].
Therefore, a communication fault action will be ignored. Take
precautions to verify that the setting does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, a
disconnected cable).
255.255.255.255
[BBMD Cfg 1]
[BBMD Cfg 2]
[BBMD Cfg 3]
[BBMD Cfg 4]