Installing the Option Module Chapter 2
Table 1 - Drive and Option Module Start-Up Status Indications
After verifying correct operation, swing down the drive HIM bezel to its closed
position and install the drive cover. For more details on status indicator
operation, see
and
Item
Name
Color
Status
Description
Drive STS Indicator
➊
STS
(Status)
Green
Flashing
Drive ready but not running, and no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing
When running, a type 2 (non-configurable alarm condition exists – drive continues to run.
When stopped, a start inhibit condition exists and the drive cannot be started (see drive
parameter 933 - [Start Inhibits]).
Steady
A type 1 (user configurable) alarm condition exists, but the drive continues to run.
Red
Flashing
A major fault has occurred. Drive will stop. Drive cannot be started until fault condition is
cleared.
Steady
A non-resettable fault has occurred.
Red/Yellow
Flashing Alternately
A minor fault has occurred. Use drive parameter 950 - [Minor Flt Config] to enable. If not
enabled, acts like a major fault. When running, the drive continues to run. System is
brought to a stop under system control. The fault must be cleared to continue.
Yellow/Green
Flashing Alternately
When running, a type 1 alarm exists.
Green/Red
Flashing Alternately
Drive firmware is updating.
Option Module Status Indicators
➋
PORT
—
Off
The option module is not powered or connected properly to the drive.
Red
Flashing
The option module is not receiving any communication from the drive.
Steady
The option module detected a duplicate or invalid port ID.
Green
Flashing
Normal operation. The option module is establishing communication with drive. It will
turn steady green or red.
Steady
Normal operation. The option module is properly connected and communicating with the
drive.
Orange
Steady
The brand of the option module and drive do not match.
➌
MOD
—
Off
The option module is not powered or connected properly to the drive.
Red
Flashing
The option module has failed the firmware test or a firmware update is in progress.
Steady
The option module has failed the hardware test.
Green
Flashing
Normal operation. The option module is operating but is not transferring I/O data to a
controller.
Steady
Normal operation. The option module is operating and transferring I/O data to a
controller.
➍
NET A
—
Off
The option module is not powered or connected properly to the network. The link is
inactive.
Red
Flashing
Any error in packet validation and/or execution is considered a network configuration
error.
Steady
Any failure in self-test on the external Ethernet controller is considered a network
controller error.
Green
Steady
Normal operation. The option module is properly connected and communicating on the
network.