Setting web page access – Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual
Page 32

32
Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter 3 Configuring the Option Module
Setting Web Page Access
By using a web browser to access the IP address set for the option module, you
can view the option module web pages for information about the module, the
drive, and other DPI devices connected to the drive, such as HIMs or converters.
By default, the option module web pages are disabled. To enable the option
module web pages, do the following.
1.
Set
Device Parameter 26 - [Web Enable] to ‘1’ (Enabled).
2.
Reset the option module; see
Resetting the Option Module on page 33
so
that the change takes effect.
For more details on the option module web pages, see
The option module can be configured to automatically send e-mail messages to
desired addresses when selected drive faults occur and/or are cleared, and/or
when the option module takes a communication or idle fault action.
Bit 0 of Device Parameter 27 - [Web Features] is used to protect the configured
settings for e-mail messaging. By default, settings are not protected and the user
can make changes. To protect the configured settings, set the value of E-mail Cfg
Bit 0 to ‘0’ (Disabled). You can unprotect the configuration by changing Bit 0
back to ‘1’ (Enabled). E-mail messaging will always remain active regardless of
whether or not its settings are protected—unless e-mail messaging was never
configured. For more information about configuring option module e-mail
messaging or to stop e-mail messages, see
Configure E-mail Notification Web
.
Bit 0 is the right-most bit. In the example above, it equals ‘1’ (Enabled).
Changes to this parameter take effect immediately. A reset is not required.
Stopped
0.00 Hz
AUTO
F
Edit Web Enable
Disabled
0
0 << 1
ESC
▲
▼
ENTER
Value Description
0
Disabled (Default)
1
Enabled
Bit
Description
0
E-mail Cfg (Default = 1 = Enabled)
1...7
Not Used
AUTO
F
Stopped
0.00 Hz
Edit Web Features
xxxx xxx1
E-mail Cfg
ESC
ENTER