Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual
Page 48

48
Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
Chapter 5 Troubleshooting
12
DPI Host Reset
The drive sent a reset event message.
13
DPI Baud 125kbps
The option module detected that the drive was communicating at 125 Kbps.
14
DPI Baud 500kbps
The option module detected that the drive was communicating at 500 Kbps.
15
DPI Host Invalid
The option module was connected to an incompatible product.
16
DPI Dup Port
Another peripheral with the same port number is already in use.
17
DPI Type 0 Logon
The option module has logged in for Type 0 control.
18
DPI Type 0 Time
The option module has not received a Type 0 status message within the specified time.
19
DPI DL Logon
The option module has logged into a Datalink.
20
DPI DL Error
The drive rejected an attempt to log in to a Datalink because the Datalink is not supported or is used by another
peripheral.
21
DPI DL Time
The option module has not received a Datalink message within the specified time.
22
DPI Ctrl Disable
The option module has sent a ‘Soft Control Disable’ command to the drive.
23
DPI Ctrl Enable
The option module has sent a ‘Soft Control Enable’ command to the drive.
24
DPI Msg Timeout
A Client-Server message sent by the option module was not completed within 1 second.
25
DPI Manual Reset
The option module was reset by changing its Reset Module parameter.
SI Events
26
SI Online
The option module has logged into the Serial Interface Communications.
27
SI Logon Error
The option module failed to log into the Serial Interface.
28
SI Comm Fault
The Serial Interface Communications has faulted.
Network Events
29
Net Link Up
A network link was available for the option module.
30
Net Link Down
The network link was removed from the option module.
31
Net Dup Address
The option module uses the same address as another device on the network.
32
Net Comm Fault
The option module detected a communications fault on the network.
33
Net Sent Reset
The option module received a reset from the network.
34
Net IO Close
An I/O connection from the network to the option module was closed.
35
Net Idle Fault
The option module received ‘idle’ packets from the network.
36
Net IO Open
An I/O connection from the network to the option module has been opened.
37
Net IO Timeout
An I/O connection from the network to the option module has timed out.
38
Net IO Size Err
The option module received an incorrectly sized I/O packet.
39
PCCC IO Close
The device sending PCCC Control messages to the option module has set the PCCC Control Timeout to zero.
40
PCCC IO Open
The option module has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a
non-zero value).
41
PCCC IO Timeout
The option module has not received a PCCC Control message for longer than the PCCC Control Timeout.
42
Msg Ctrl Open
The timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing
control messages to be sent to the option module.
43
Msg Ctrl Close
The timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing control
messages to be sent to the option module.
44
Msg Ctrl Timeout
The timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.
45
Peer IO Open
The option module received the first Peer I/O message.
Table 5 - Option Module Events (Continued)
Code
Event Text
Description