Rockwell Automation 20-750-BNETIP BACnet/IP Option Module User Manual
Page 41

Rockwell Automation Publication 750COM-UM005B-EN-P - June 2014
41
Using BACnet Services and Objects Chapter 4
AV21
Mailbox1 Param
Read/write any drive parameter.
To read a drive parameter, write the number for the desired parameter to
the Mailbox Param object, and then read the Mailbox value object.
To write a drive parameter, write the number for the desired parameter to
the Mailbox Param object, and then write the desired value to the
Mailbox Value object.
—
✔
✔
AV22
Mailbox1 Value
—
✔
✔
AV23
Mailbox2 Param
—
✔
✔
AV24
Mailbox2 Value
—
✔
✔
AV25
Mailbox3 Param
—
✔
✔
AV26
Mailbox3 Value
—
✔
✔
AV27
Mailbox4 Param
—
✔
✔
AV28
Mailbox4 Value
—
✔
✔
AV29
Mailbox5 Param
—
✔
✔
AV30
Mailbox5 Value
—
✔
✔
AV31
Mailbox6 Param
—
✔
✔
AV32
Mailbox6 Value
—
✔
✔
AV33
Mailbox7 Param
—
✔
✔
AV34
Mailbox7 Value
—
✔
✔
AV35
Mailbox8 Param
—
✔
✔
AV36
Mailbox8 Value
—
✔
✔
Binary Input (BI) Objects
BI0
Digital Input 0
Read the state of Digital Input 0 on the drive’s OBJECTS terminal block.
220 (Bit 0)
✔
✔
B11
Digital Input 1
Read the state of Digital Input 1 on the drive’s OBJECTS terminal block.
220 (Bit 1)
✔
—
BI2
Digital Input 2
Read the state of Digital Input 2 on the drive’s OBJECTS terminal block.
220 (Bit 2)
✔
—
Binary Output (BO) Objects
BO0
Output Relay 0
Read/write the state of Output Relay 0
227
✔
—
Binary Value (BV) Objects
BV0
RUN Ready
Read the drive’s RUN Ready status.
Logic Status
Word, Bit 0
✔
✔
BV1
Active
Read the drive’s Active status, which is enabled if the drive is running.
Logic Status
Word, Bit 1
✔
✔
BV2
Forward/Reverse
Read the drive’s Actual Direction status, which is active if the drive is
running.
Logic Status
Word, Bit 3
✔
✔
BV3
Fault
Read the drive’s Fault status, which is active if the drive is faulted.
Logic Status,
Word, Bit 7
✔
✔
BV4
Alarm
Read the drive’s Alarm status, which is active if the drive has an alarm.
Logic Status
Word, Bit 6
✔
✔
BV5
At Setpt Spd
Read the drive’s Setpd Spd status, which is enabled if the drive is running
at the specified speed reference.
Logic Status
Word, Bit 8
✔
✔
BV6
Manual Active
Read the drive’s Manual Mode setting.
0 = Manual Mode Not Active; 1 = Manual Mode Active
Logic Status
Word, Bit 9
✔
✔
Table 3 - BACnet Object Descriptions and Supported Drives (Continued)
Object
Name
Use this Object to...
Drive
Parameter
Number
PowerFlex 750-
Series Drive
753
755