RS485 (DSI) Protocol

C-5

Reading (03) Drive Error Codes

The PowerFlex 4 Error Code data can be read via the network by sending
Function Code 03 reads to register address 8449 (Drive Error Codes).

Reading (03) and Writing (06) Drive Parameters

To access drive parameters, the Modbus register address equals the
parameter number. For example, a decimal “1” is used to address
Parameter d001 [Output Freq] and decimal “39” is used to address
Parameter P039 [Accel Time 1].

Additional Information

Refer to

http://www.ab.com/drives/

for additional information.

Logic Status

Address (Decimal)

Value (Decimal)

Description

8449

0

No Fault

2

Auxiliary Input

3

Power Loss

4

Undervoltage

5

Overvoltage

6

Motor Stalled

7

Motor Overload

8

Heatsink Overtemperature

12

HW Overcurrent (300%)

13

Ground Fault

29

Analog Input Loss

33

Auto Restart Tries

38

Phase U to Ground Short

39

Phase V to Ground Short

40

Phase W to Ground Short

41

Phase UV Short

42

Phase UW Short

43

Phase VW Short

63

Software Overcurrent

64

Drive Overload

70

Power Unit Fail

80

AutoTune Fail

81

Communication Loss

100

Parameter Checksum Error

122

I/O Board Fail