Essential requirements for ce compliance, Installation/wiring 1-21 – Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 31
Installation/Wiring
1-21
Essential Requirements for CE Compliance
Conditions 1-3 listed below must be satisfied for PowerFlex drives to
meet the requirements of EN61800-3.
1. Grounding as described in
. Refer to
for
additional grounding recommendations.
2. Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.
3. Allowable cable length in
Table 1.I Allowable Cable Length
(1)
Refer to
for details on optional external filters.
(2)
Equivalent to EN55011 Class A.
(3)
Equivalent to EN55011 Class B.
Figure 1.6 Connections and Grounding
(1)
First Environment Unrestricted Distribution installations require a shielded enclosure.
Keep wire length as short as possible between the enclosure entry point and the EMI
filter.
(2)
Integral EMI filters are available on 240V, 1-Phase drives.
Filter Type
EN61800-3 First Environment
Restricted Distribution or
Second Environment
(2)
EN61800-3 First Environment
Unrestricted Distribution
(3)
Integral
10 meters (33 feet)
1 meter (3 feet)
External - S Type
(1)
10 meters (33 feet)
1 meter (3 feet)
External - L Type
(1)
100 meters (328 feet)
5 meters (16 feet)
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
EMI Fittings and Metal Conduit
IP 30/NEMA 1/UL Type 1
Option Kit
Shielded Enclosure
(1)
Building Structure Steel
Enclosure Ground Connection
(2)
EMI Filter
L1'
L2'
L3'
L1
L2
L3
Shielded Motor Cable