Rockwell Automation 22A PowerFlex 4 User Manual FRN 6.xx User Manual
Page 71
Troubleshooting
4-7
Motor and/or drive will not accelerate to commanded speed.
Motor operation is unstable.
Drive will not reverse motor direction.
Cause(s)
Indication
Corrective Action
Acceleration time is excessive. None
Reprogram
[Accel Time 1] or
[Accel Time 2].
Excess load or short
acceleration times force the
drive into current limit, slowing
or stopping acceleration.
None
Compare
[Output Current] with
[Current Limit].
Remove excess load or reprogram
[Accel Time 1] or
[Accel
Time 2].
Check for improper
[Boost
Select] setting.
Speed command source or
value is not as expected.
None
Verify
[Commanded Freq].
Check
[Control Source] for the
proper Speed Command.
Programming is preventing the
drive output from exceeding
limiting values.
None
Check
[Maximum Freq] to
insure that speed is not limited by
programming.
Cause(s)
Indication
Corrective Action
Motor data was incorrectly
entered.
None
1. Correctly enter motor nameplate
data into
.
[Compensation].
3. Use
[Boost Select] to
reduce boost level.
Cause(s)
Indication
Corrective Action
Digital input is not selected for
reversing control.
None
. Choose correct input
and program for reversing mode.
Digital input is incorrectly
wired.
None
Check input wiring.
Motor wiring is improperly
phased for reverse.
None
Switch two motor leads.
Reverse is disabled.
None
Check
[Reverse Disable].